SmartGen | CANBUS Relay Module-SGCAN300


RS232, RS485, CANBUS Theoretical Communication Distance:

1.Theoretical transmission distance of RS-232 protocol is 10 meters;
2.Theoretical transmission distance of RS-485 protocol is 1000 meters;
3.CANBUS theoretical transmission distance is shown in the table below:

The stability and timeliness of data transmission can be optimized by selecting appropriate communication interface and baud rate in equipment monitoring. In the application of multi-units parallel system, there may be a situation that multiple gensets are far away (more than 250 meters). In order to meet the requirements of long-distance communication, SmartGen will launch a CANBUS relay module-SGCAN300 in the near future.

Main Features

1.Conversion of CANBUS and optical fiber;
2.Conversion of RS485 and optical fiber;
3.CANBUS Relay;
4.Dial switch set RS485, CAN communication baud rate;
5.DC8-35V continuous power supply, DC reverse connection protection;
6.RS485 interface (isolated, half-duplex, baud rate 9600bps, 19200bps optional);
7.CAN interface (isolated, baud rate 50kbps, 125kbps, 250kbps, 500kbps optional);
8.Optical fiber interface, transmission distance:>2km.

Communication Conversion Diagram

Typical Application Diagram of MSC1 and Optical Fiber Conversion

Typical Application Diagram of RS485 and Optical Fiber Conversion

Typical Application Diagram of MSC1 and MSC2

Description of LED indicator

 

Case Dimensions and Installation

 

SGCAN300 Communication Relay Diagram

 

SGCAN300 Application Case